Transformer on Load

In this topic, you study Transformer on Load.

Let the equivalent circuit shown in Fig. 3.15 represent the actual transformer. When the primary winding of a transformer is connected across the ac supply of voltage  with no load on the secondary side (i.e. with secondary winding open circuited), as already mentioned earlier, its primary winding draws a small current  from the supply (Fig. 3.13). This current has two components. The magnetizing component  sets up mutual flux which is in time phase with it. This flux induces emfs  and  in the primary and secondary windings. The other component of  i.e. core-loss component provides the core losses.

Now, if the load is put on the transformer by connecting an impedance of finite value across its secondary winding, a current  flows through the secondary winding causing voltage drops in its resistance  and leakage reactance . Hence the secondary terminal voltage  under this condition is given by

E, – 12 E, -12 Z,

(3.13)

The phase relationship between the secondary current  and the secondary terminal voltage  is determined by the characteristics of the load. To neutralize the demagnetizing effect of secondary current , primary draws additional current in anti-phase with  such that,

 

Thus, the primary current Il on load can be considered as having two components 12 and . Hence,

 

This primary current Il causes voltage drops in the resistance  and leakage reactance  of the primary winding. The primary impressed voltage  is therefore given by the phasor sum of  (part of the applied voltage balancing ) and the drops  and  i.e. The cosine of the angle between  and gives the power factor on the primary side of the transformer. The phasor diagram for the transformer on load can therefore be constructed as follows

Assume first the load to be inductive in nature and having a power factor of . Starting with voltage , (i.e. taking it as reference phasor),  is drawn lagging behind  by The magnitude of  is of course decided by the load impedance. The  phasor is drawn in phase with the current  and the phasor  leading it by 90o. The phasor sum of V2,  and  is . The emf  is in time phase with . The load component  of the primary current to neutralize the demagnetizing effect of  is drawn opposite to . The total current Fig. 3.16 : Phasor diagram of a transformer with inductive load  in the primary is obtained by the phasor sum of the no-load currents  and  . The current

is drawn such that its magnitude is equal to the current taken by the primary when the transformer is on no load. The angle of lag of  behind  (i.e. ) is assumed to be equal to the angle between the primary impressed voltage  and the no-load primary current (i.e. when  is zero). The Resistance and reactance drops  and  drawn in phase with the current  and leading  by 90o respectively. Finally, the primary impressed voltage  is obtained from the phasor sum of ,  and . Fig. 3.16 shows the complete phasor diagram of a transformer. If is the phasor difference between  and then obviously the power factor of the primary side of the transformer is . The same method can be used for constructing the phasor diagram for the secondary load of any nature.

Figs. 3.17 (a) and (b) show the phasor diagrams for the resistive (with unity power factor)

and capacitive (with leading power factor) loads.

Fig. 3.17 : Phasor diagrams of a transformer with

(a) Resistive load, (b) Capacitive load

Incidentally, it should be noted that the no-load current  is of small magnitude in comparison with the total primary current on full load. Therefore, if it be neglected,

Then from the Equation (3.14), we have

or,

 

i.e. the primary and secondary currents are inversely proportional to the respective turns.

Leave a Comment

error: Content is protected !!