Open Delta Connection of Transformer

In this topic, you study Open Delta Connection of Transformers – Theory, Diagram, and Derivation.

If one transformer of the delta delta connected three phase transformers is disconnected due to some fault in it, the remaining two transformers make an open-delta or V–V connection as shown in Figure 1. The open-delta connection supplied a three-phase load with a rating reduced to about 57.7

Figure 1 Open-delta connection by two single-phase transformers

Let us examine the VA rating of delta-delta connected transformers and open-delta transformers as shown in Figure 2.

(1)

(2)

The ratio of Equation 1 and Equation 2 as,

  • Delta-delta connection
  • Open-delta connection

Figure 2 Delta-delta connection and V–V connection for comparison (only secondary shown)

This shows that the load carried by open delta connected transformers is only 57.7 percent of the original load.

Published by

Electrical Workbook

We provide tutoring in Electrical Engineering.